Products | Transmitter EXL-IM-9182
Ex-i Transmitter EXL-IM-9182-10-51-11s C2305 TMU
ATEX 2014/34/EU | zone 0, 1, 2, 20, 21, 22
Transmitter °C, %rH, ΔP
with intrinsic Ex-i safe circuit
Description – Ex-i transmitter EXL-IM-9182-10-51-11s C2305 TMU
- The Ex-i transmitter is used for intrinsically safe operation of temperature sensors or resistance transmitters
- Virtually all conventional sensors, such as Pt100, Pt500, thermocouples and potentiometers with 2-3-4-wire connection, can be connected
- The sensors are for installation in hazardous locations
- The transmitter must be installed in safe area
- Simple configuration via software or DIP-switches
Technical data
Electric supplyInput (passive sensors)OutputDisplay / IndicationHousing protectionAmbient temperaturePower supplyMountingWeightMeasurementsExplosion proof for allInstallation area of transmitter (module)Installation area of sensor*Certification*depending on sensor
EXL-IM-9182
24 V DC, inverse-polarity protectionPt100, Pt500, Pt1000, Ni100, Ni500, Ni1000, 0...1.000 Ohm4...20 mA, with additional plug 0...10 VLED operation indicationIP 30-20°...+70°CTerminals, IP 20rail mounting DIN NS35/15, NS35/7,5approx. 195 gW × H × D = 17,6 × 99 × 114,5 mmgases, mists, vapours, dustsafe areazone 0, 1, 2, 20, 21, 22ATEX 2014/34/EU and others
Delivery – EXL-IM-9182
- Ex-i module for rail mounting according DIN...
Accessories – EXL-IM-9182
- Optional: analog sensors series ExSens
- Plug 0-10V-9182 for output 0...10 V (installation in safe area)
- N1 supply unit, input 120...240 VAC, output 24 VDC, max. 0,5 A, max. 4 pcs. EXL-IM-... connectable. Supply unit is required only in case of 120...240 VAC supply!